4 Operation
4.1 Checklist for commissioning
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 111
4 Operation
4.1 Checklist for commissioning
Before placing the frequency converter into operation, use the checklist
below to make sure that all the following requirements are met:
No. Activity Notes
1
Mounting and wiring have been carried out in accordance with
the corresponding instruction leaet ( IL04020009Z,
IL04020013Z, IL04020024ZU).
2
All wiring and line section leftovers, as well as all the tools used,
have been removed from the variable frequency drive’s
proximity.
3
All connection terminals in the power section and in the control
section were tightened with the specified torque.
4
The lines connected to the output terminals (U, V, W, DC+, DC-,
BR) of the variable frequency drive are not short-circuited and
are not connected to earth (PE).
5
The variable frequency drive has been earthed properly (PE).
6
All electrical connections in the power section (L1/L, L2/N, L3, U,
V, W, DC+, DC-, BR, PE) have been connected properly while
taking into account the degree of protection and have been
dimensioned in line with the corresponding requirements.
7
Each single phase of the supply voltage (L or L1, L2, L3) is
protected with a fuse.
8
The variable frequency drive and the motor are adapted to the
mains voltage.
( Section 1.4.1, “Rated operational data on the nameplate“,
page 12, connection type (star, delta) of the motor tested).
9
The quality and volume of cooling air are in line with the
environmental conditions required for the variable frequency
drive and the motor.
10
All connected control cables comply with the corresponding stop
conditions (e.g., switch in OFF position and setpoint value
= zero).
11
The parameters that were preset at the factory have been
checked with the list of parameters ( MN04020004Z).
12
The effective direction of a coupled machine will allow the motor
to start.
13
All emergency switching off functions and safety functions are in
an appropriate condition.