6 Technical Data
6.1 General rating data
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 129
6 Technical Data
6.1 General rating data
Technical data Symbol Unit Value
General
Standards EMC: EN 61800-3:2004+A1-2012
Radio interference: EN 55011: 2010
Safety: EN 61800-5: 2007
Degree of protection: EN 60529: 1992
Certifications and manufacturer’s declarations on conformity CE, UL, cUL, c-Tick, UkrSEPRO, Gost-R
Production quality RoHS, ISO 9001
Climatic proofing ρ
w
% < 95 %, average relative humidity (RH), 
non-condensing (EN 50178)
Ambient air temperature
Operational
IP20 (NEMA 0) ϑ °C -10 - +50 (frost-free and condensation-free)
-10 - +45 for DC1-12011… and DC1-32011…,
for UL compliance over a period of 24 hours
IP66 (NEMA 4X) ϑ °C -10 - +40 (frost-free and condensation-free)
Note:
Operation within a temperature range of 40 to 50 °C 
does not conform to UL listing.
Storage ϑ °C -40 - +60
MTBF (mean time between failures)  Years 157
Electrostatic discharge (ESD, EN 61000-4-2:2009 U kV ±4, contact discharge
±8, air discharge
Fast transient burst (EFT/B, EN 61000-4-4: 2004) U kV ±1, at 5 kHz, control signal terminal
±2, at 5 kHz, motor connection terminals,
single-phase mains connection terminals
±4, at 5 kHz, three-phase mains connection terminals