4 Operation
4.5 Handling the keypad
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 121
4.5.4 Extended parameter set
Table 17: Enabling and disabling access to the extended parameter set
Commands Description
Enabling access to the extended parameter set
Press the OK button and hold it down for two seconds in 
order to access the parameter interface
The display will show the parameter that was last used.
Use the ▲ and ▼ buttons to select parameter P-14
Press the OK button.
Use the ▲ and ▼ buttons to enter the password set with 
P-37 (default setting: 101)
Press the OK button to confirm
The extended parameter set (parameters > P-14 and 
display values P00-…) will now be available.
Disabling access to the extended parameter set
Use the ▲ and ▼ buttons to set a value for P-14 that 
does not match the password (P-37).
Press the OK button to confirm
Only the “basic parameters”, P-01 to P-14, will be 
accessible now.
→
The extended parameter set (default setting for P-37 = 101) 
contains parameters P-01 to P-59.
Additional parameters P-60 to P-68 can be configured for 
specific applications. The corresponding password is 201 in 
parameter P-37 (value of P-37 + 100).