EasyManua.ls Logo

Eaton PowerXL DC1 - 4.3 Commissioning with control signal terminals (default settings)

Eaton PowerXL DC1
179 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 DC1 device series
1.7 Selection criteria
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 27
1.7 Selection criteria
Select the variable frequency drive according to the supply voltage U
LN
of
the supply system and the rated operational current of the assigned motor.
The circuit type ( / ) of the motor must be selected according to the
supply voltage.
The variable frequency drive’s rated output current I
e
must be greater than or
equal to the rated motor current.
Figure 12: Selection criteria
When selecting the drive, the following criteria must be known:
Mains voltage = rated operating voltage of the motor (e. g. 3~ 400 V),
Type of motor (e.g., three-phase asynchronous motor)
Rated motor current (recommended value, dependent on the circuit type
and the power supply)
Ambient conditions: ambient temperature, control cabinet installation
with IP20 degree of protection or direct local installation with IP66
degree of protection.
Example based on figure 12
Mains voltage: 3~ 400 V, 50 Hz
Star-connected circuit (400 V)
Rated operational current: 1.9 A (400 V)
Control panel installation
IP20 degree of protection
Ambient air temperature max. 50 °C without output reduction, IP20
Variable frequency drive that should be selected: DC1-342D2FN-A20N
DC1-34…: 3-phase main terminal, rated operating voltage: 400 V
DC1-…2D2…: 2.2 A – The variable frequency drive’s rated operational
current (output current) guarantees that the motor will be supplied with
the required rated operational current (1.9 A).
1410 min
230/400 V 3.2/1.9 A
50 Hz
-1
0,75 KW
cos ϕ 0.79
P-07
P-08
P-10
P-09
L1/L
L2/N
L3
U
V
W
1
2
3
4
5
6
7
8
9
10
11

Table of Contents

Other manuals for Eaton PowerXL DC1

Related product manuals