6 Technical Data
6.2 Specific rated operational data
138 DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com
6.2.4 DC1-34…device series
Size Symbol unit
2D2 4D1NN
4D1FN
4D1NB
4D1FB
5D8 9D5
Rated operational current  I
e
A 2.2 4.1 4.1 5.8 9.5
Overload current for 60 s every 600 s i
l
A
3.3 6.15 6.15 8.7 14.25
Starting current for 2 s every 20 s A
3.85 7.18 7.18 10.15 16.63
Apparent power at rated operation 
400 V
SkVA
1.52 2.84 2.84 4.02 6.58
Apparent power at rated operation 
480 V
SkVA
1.83 3.41 3.41 4.82 7.9
Assigned motor power
at 400 V, 50 Hz P kW 0.75 1.5 1.5 2.2 4
at 440 - 480 V, 60 Hz P HP
1 2 2 3 5
Power side (primary side):
Number of phases 3 3 3 3 3
Rated operating voltage U
LN
 V
380 V - 10 % - 480 V + 10 %, 50/60 Hz
342 - 528 V ±0 %, 48 - 62 Hz ±0 %
Input current (phase current) I
LN
A
3.5 5.6 5.6 7.5 11.5
Minimum braking resistance R
B
 Ω
– – 250 200 120
Switching frequency (pulse frequency)
Default Setting f
PWM
kHz 16 16 16 16 16
Setting range f
PWM
kHz
4 - 32 4 - 32 4 - 32 4 - 32 4 - 32
Maximum leakage current to earth 
(PE),
Without motor
I
PE
mA
< 1 < 1 < 1 < 1 < 1
Efficiency η
0.92 0.95 0.95 0.95 0.97
Heat dissipation at I
e
 (150 %) P
V
CO
33.75 66.5 66.5 101.2 136
fan, built-in
✓ ✓ ✓ ✓ ✓
Size
FS1 FS1 FS2 FS2 FS2