2 Engineering
2.2 Electrical power network
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 37
2.2 Electrical power network
2.2.1 Mains terminal and configuration
DC1 variable frequency drives can be connected to and run on all neutral 
point-grounded AC supply systems (TN-S, TN-C, TT grounding systems; 
please refer to IEC 60364) without any limitations.
Figure 14: AC supply systems with earthed center point
The connection and operation of variable frequency drives to asymmetrically 
grounded TN networks (phase-grounded delta network “Grounded Delta”, 
USA) or non-grounded or high-resistance grounded (over 30 ) IT networks is 
only conditionally permissible (internal radio interference suppression filters).
DC1-…-A20N variable frequency drives can be connected to corner-
grounded systems or IT grounding systems (not grounded, insulated).
When versions featuring an internal radio interference suppression filter
(DC1-…FN-A20N, DC1-…FB-A20N) are connected to one of these systems, 
the EMC screw(s) needs to be removed and the internal radio interference 
suppression filter needs to be disconnected 
TN-S TN-C TT
→
While planning the project, consider a symmetrical distribution 
to the three main phase conductors, if multiple variable 
frequency drives with single-phase supplies are to be 
connected. The total current of all single phase consumers is 
not to cause an overload of the neutral conductor (N-conductor).
→
Operation on non-earthed networks (IT) requires the use of 
suitable insulation monitoring relays (e.g. pulse-code 
measurement method)
→
In networks with an earthed phase conductor, the maximum 
phase-earth voltage must not exceed 300 V AC.
→
Measures for electromagnetic compatibility are mandatory in a 
power drive system, to meet the legal standards for EMC- and 
Low Voltage Directive. Good earthing measures are a 
prerequisite for the effective Use of further measures such as 
screen earth kit or filters here. Without respective grounding 
measures, further steps are superfluous.