6.5 Fuses
The Eaton circuit-breakers and fuses listed below are examples and can be 
used without additional measures. If you use other circuit-breakers and/or 
fuses, make sure to take their protection characteristic and operational 
voltage into account. When using other circuit-breakers, it may be necessary 
to also use fuses depending on the circuit-breaker’s model, design, and 
settings. There may also be limitations concerning the short-circuit capacity 
and the supply network’s characteristic, and these must also be taken into 
account when selecting circuit-breakers and/or fuses.
Table 24: Protective devices
Symbol
Description
 Miniature circuit breakers
FAZ-B…/1N: 1 pole + N
FAZ-B…/2: 2 pole
FAZ-B…/3: 3 pole
Rated operating voltage: 230/400 V AC
Switching capacity: 15 kA
Motor-Protective Circuit-Breakers
PKM0…, PKZM4…: 3 pole
Rated operating voltage: 690 V AC
Switching capacity:
• PKM0: 150 kA to 12 A and 50 kA to 32 A
•PKZM4: 50 kA
Fuse
Rated operating voltage: 500 V AC
Switching capacity: 50 kA
Size: DII, E27 / DIII, E33
Fuse base: S27… / S33…
Fuse Class J
Rated operating voltage: 600 V AC
Switching capacity: 300 kA 
Fuse bases: 
• up to 30 A: J60030…
• 35 - 60 A: J60060…
• 70 - 100 A: JM60100…