6 Technical Data
6.4 Cable cross-sections
144 DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com
DC1-32046…
FS4 16 5 50.1 16 6 46 10 6
Mains voltage 400 V
Supply voltage (50/60 Hz) U
LN
380 (-10 %) - 480 (+10 %) V
U
e
400 V AC, three-phase / U
2
400 V AC, three-phase
DC1-342D2…
FS1 8 8 3.5 1.5 14 2.2 1.5 14
DC1-344D1NN…
FS1 8 8 5.6 1.5 14 4.1 1.5 14
DC1-344D1FN…
FS1 8 8 5.6 1.5 14 4.1 1.5 14
DC1-344D1NB…
FS2 8 8 5.6 1.5 14 4.1 1.5 14
DC1-344D1FB…
FS2 8 8 5.6 1.5 14 4.1 1.5 14
DC1-345D8…
FS2 8 8 7.5 1.5 14 5.8 1.5 14
DC1-349D5…
FS2 8 8 11.5 2.5 12 9.5 1.5 14
DC1-34014…
FS3 8 8 17.2 4 10 14 1.5 14
DC1-34018…
FS3 8 8 21.2 4 10 18 2.5 10
DC1-34024…
FS3 8 8 27.5 8 8 24 4 10
DC1-34030…
FS4 16 5 34.2 16 8 30 6 8
DC1-34039…
FS4 16 5 44.1 16 6 39 10 8
DC1-34046…
FS4 16 5 51.9 16 5 46 10 6
1) AWG = American wire gauge
kcmil = Thousands of circular mils (1 kcmil = 0.5067 mm²)
2) Maximum motor cable length: 200 m
When using screened motor cables with a length greater than 100 m (up to 200 m), a motor choke must be used (dv/dt limiting).
Device Type
Frame
size
Maximum
terminal capacity
Input current
I
LN
Cross-sectional area/
gauge that should be
used for the power
supply (L1/L, L2/N, L3, PE)
Output
current (rated
operational
current) I
e
Cross-sectional area/
gauge that should be
used for the motor
connection (U, V, W, PE)
mm
2
AWG/
kcmil
1)
A mm
2
AWG/
kcmil
1)
A mm
2
AWG/
kcmil
1)