3 Installation
3.6 Electrical Installation
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 95
3.6.3 Thermistor connection
Motor thermistors and motor thermal switches (Thermoclick) can be 
connected to control signal terminal 4 (DI3 = digital input 3) in order to 
provide protection against thermal motor overloads.
In this case, parameter P-15 must be used to select the EXTFLT (external 
fault) setting for DI3, and parameter P-47 must be set to a value of 6
(Ptc-th). 
Figure 60: Thermistor connection
The thermistors and thermal switches used must be PTC-type units (PTC 
characteristic, positive temperature coefficient).
The tripping range must fall within a resistance value range of approximately 
2.5 - 3 k, while the reset range must fall within a range of 1.9 - 1 k.