7 Accessories
7.1 Device-specific accessories
168 DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com
7.1.3 DXC-EXT-2RO1AO output expansion
Figure 90: DXC-EXT-2RO1AO
Expansion module DXC-EXT-2RO1AO was developed with HVAC
applications in mind. It can switch the “Drive running” and “Shutdown due
to fault” messages with two separate relays (K1, K2).
Table 35: Specific technical data DXC-EXT-2RO1AO
Technical Specification Unit Value
Output switching voltage
K1 (control signal terminals 12, 13) V 250 AC / 230 DC
K2 (control signal terminals 10, 11) V 250 AC / 220 DC
AO V 0 - 10 DC
Relay switching current
K1 (control signal terminals 12, 13) A 1
K2 (control signal terminals 10, 11) A 1
AO mA < 20
Operating Temperature °C -10 - +50
Degree of protection (without the connection
pins being covered by the DC1’s control signal
terminal block)
IP00
For detailed instructions on how to install the module, please
refer to instruction leaflet IL04012014Z.
NOTICE
Internal relay K1 is looped with the expansion module, meaning
it can only conduct a lower current ( 1A).