4 Operation
4.4 Commissioning with local controls
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 117
Example
Table 13: Selector switch for DC1-…A6SN
Switch position
Parameter Description
P-12 P-15
Default Setting
REV
(Anticlockwise
rotation field)
STOP FWD
(Clockwise
rotation field)
0 5 Speed control with the setpoint potentiometer on the front
Only one operating direction
STOP STOP FWD
(Clockwise
rotation field)
0 0 Speed control with the setpoint potentiometer on the front
Application: Aeration
/
De-aeration
REV
(Anticlockwise
rotating field)
with fixed
frequency
STOP FWD
(Clockwise
rotating field)
with
potentiometer
0 5 Requirement:
Control signal terminals 3 (DI2) and 4 (DI3) are connected
with a jumper.
A fan is used to supply and remove air, with the specific
action depending on the operating direction being used.
In one of these operating modes (e.g., supplying air, FWD
via DI1), the fan speed can be variably adjusted by using
the internal setpoint potentiometer .
In the other (removing air, REV via DI2 and DI3), the fan is
run with the speed configured as a set value in parameter
P-20 (default setting = 15 Hz).
REV FWD
0
REV FWD
0
REV FWD
0