6 Technical Data
6.6 Mains contactors
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 149
Table 26: Mains contactors
Device Type
Input current Mains contactor (thermal current AC-1)
I
LN
Type
(max. 50 
o
C and IEC)
Type
(max. 40 
o
C and UL)
A A A
Mains voltage 115 V
Supply voltage (50/60 Hz) U
LN
 110 (-10 %) - 115 (+10 %) V
U
e
 115 V AC, single-phase / U
2
 230 V AC, three-phase (internal voltage doubler)
DC1-1D2D3…
7.8 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-1D4D3…
15.8 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-1D5D8…
21.9 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
 200 (-10 %) - 240 (+10 %) V
U
e
 230 V AC, single-phase / U
2
 230 V AC, three-phase
DC1-122D3…
3.7 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-124D3…
7.5 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-127D0NN…
12.9 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-127D0FN…
12.9 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-127D0NB…
12.9 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-127D0FB…
12.9 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-12011…
19.2 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
DC1-12015…
29.2 DILEM-…+P1DILEM 50 DILEM-…+P1DILEM 50
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
 200 (-10 %) - 240 (+10 %) V
U
e
 230 V AC, three-phase / U
2
 230 V AC, three-phase
DC1-322D3…
3.4 DILEM-… 20 DILEM-… 20
DC1-324D3…
5.6 DILEM-… 20 DILEM-… 20
DC1-327D0NN…
9.5 DILEM-… 20 DILEM-… 20
DC1-327D0NB…
8.9 DILEM-… 20 DILEM-… 20
DC1-327D0FB…
8.9 DILEM-… 20 DILEM-… 20
DC1-32011…
12.1 DILEM-… 20 DILEM-… 20
DC1-32018…
20.9 DILM7-… 21 DILM7-… 22
DC1-32024…
26.4 DILM17-… 38 DILM17-… 40
DC1-32030…
33.3 DILM17-… 38 DILM17-… 40
DC1-32046…
50.1 DILM40-… 57 DILM40-… 60