6 Technical Data
6.7 Mains chokes
152 DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com
DX-LN3…
Figure 81: Mains chokes DEX-LN3… (three-phase)
Table 28: Assigned mains chokes (three-phase)
Device Type
Input
current
Mains choke, three-phase
(U
LN
max. 500 V +10 %, 50/60 Hz ±10 %)
Type (max. 50
o
C) Type (max. 40
o
C)
I
LN
I
e
I
e
A A A
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
200 (-10 %) - 240 (+10 %) V
U
e
230 V AC, three-phase / U
2
230 V AC, three-phase
DC1-322D3…
3.4 DX-LN3-004 3.7 DX-LN3-004 3.9
DC1-324D3…
5.6 DX-LN3-006 5.7 DX-LN3-006 6
DC1-327D0…
9.5 DX-LN3-010 9.5 DX-LN3-010 10
DC1-32011…
12.1 DX-LN3-016 15.2 DX-LN3-016 16
DC1-32018…
20.9 DX-LN3-025 23.7 DX-LN3-025 25
DC1-32024…
26.4 DX-LN3-040 38 DX-LN3-040 40
DC1-32030…
33.3 DX-LN3-040 38 DX-LN3-040 40
DC1-32046…
50.1 DX-LN3-060 57 DX-LN3-050 50
Mains voltage 400 V
Supply voltage (50/60 Hz) U
LN
380 (-10 %) - 480 (+10 %) V
U
e
400 V AC, three-phase / U
2
400 V AC, three-phase
DC1-342D2…
3.5 DX-LN3-004 3.7 DX-LN3-004 3.9
DC1-344D1…
5.6 DX-LN3-006 5.7 DX-LN3-006 6
DC1-345D8…
7.5 DX-LN3-010 9.5 DX-LN3-010 10
DC1-349D5…
11.5 DX-LN3-016 15.2 DX-LN3-016 16
DC1-34014…
17.2 DX-LN3-025 23.7 DX-LN3-025 25
DC1-34018…
21.2 DX-LN3-025 23.7 DX-LN3-025 25
DC1-34024…
27.5 DX-LN3-040 38 DX-LN3-040 40
DC1-34030…
34.2 DX-LN3-040 38 DX-LN3-040 40
DC1-34039…
44.1 DX-LN3-050 47.5 DX-LN3-050 50
DC1-34046…
51.9 DX-LN3-060 57 DX-LN3-060 60