EasyManua.ls Logo

Eaton PowerXL DC1 - Page 17

Eaton PowerXL DC1
179 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 DC1 device series
1.4 Rated operational data
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 13
Nameplate inscription
The inscription of the nameplate has the following meaning (example):
Inscription
Meaning
DC1-344D1FB-A20N Part no.:
DC1 = DC1 series variable frequency drive
3 = Three-phase mains connection / three-phase motor connection
4 = 400 V mains voltage category
4D1 = 4.1 A rated operational current (4-decimal-1, output current)
F = Integrated radio interference suppression filter
B = Integrated brake chopper
A = LED display (7-segment text display)
20 = IP20 degree of protection
N = basic device
Input
Rated operational data of mains connection
Three-phase AC voltage (U
e
3~ AC),
380 - 480 V voltage, 50/60 Hz frequency, input phase current (4.3 A).
Output
Load side (motor) rated operational data:
Three-phase AC voltage (0 - U
e
), output phase current (4.1 A), output frequency
(0 - 500 Hz)
Assigned motor output:
1.5 kW with a voltage of 400 V/2 HP with a voltage of 460 V for a four-pole,
internally cooled or surface-cooled three-phase asynchronous motor (1500 rpm at
50 Hz/1800 rpm at 60 Hz)
Serial No.:
Serial number
IP20
Degree of protection of the housing: IP 20, UL (cUL) Open Type
Software
Software version (1.20)
25072012
Manufacturing date: 07-25-2012
Max amb. 50 °C
Maximum permissible ambient air temperature (50 °C)
variable frequency drive is an electrical apparatus.
Read the manual (in this case MN04020003Z-EN) before making any electrical
connections and commissioning.
a

Table of Contents