EasyManua.ls Logo

Eaton PowerXL DC1 - Page 81

Eaton PowerXL DC1
179 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
3.6 Electrical Installation
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 77
3.6.1.1 Terminals in power section for units with IP20 degree of protection
Table 6: Terminals (IP20)
Size Terminals Description
FS1 Connection with single-phase supply voltage:
DC1-1D… (115 V)
DC1-12… (230 V)
Remark:
Connection to terminal L3 not permissible!
Connection with three-phase supply voltage:
DC1-32… (230 V)
DC1-34… (400 V, 480 V)
Motor connection for three-phase motors:
DC1-1D… (230 V)
DC1-12… (230 V)
DC1-32… (230 V)
DC1-34… (400 V, 460 V)
FS2, FS3
Connection with single-phase supply voltage (115 V, 230 V):
DC1-1D (115 V)
DC1-12 (230 V)
Remark:
Connection to terminal L3 not permissible!
DC-: Negative DC link connection if using an external DC power supply
or DC link coupling.
The terminal’s plastic cover can be removed if necessary.
Connection with three-phase supply voltage:
DC1-32… (230 V)
DC1-34… (400 V, 480 V)
Remark:
DC-: Negative DC link connection if using an external DC power supply
or DC link coupling.
The terminal’s plastic cover can be removed if necessary.
Motor connection for three-phase motors:
DC1-1D… (230 V)
DC1-12… (230 V)
DC1-32… (230 V)
DC1-34… (400 V, 460 V)
Remark:
DC+: Positive DC link connection if using an external DC power supply,
DC link coupling, or braking chopper.
The terminal’s plastic cover can be removed if necessary.
BR: Terminal for brake resistor (braking chopper output).
The terminal’s plastic cover can be removed if necessary.
L1/L L2/N L3
LN
PE
L1/L L2/N L3
L1 L2
PE
L3
UVW
PES
M
3
DC- L1/L L2/N L3
LN
PE
DC- L1/L L2/N L3
L1 L2
PE
L3
PES
DC+ BR U V W
R
B
M
3

Table of Contents

Other manuals for Eaton PowerXL DC1

Related product manuals