String Sizing continued…
Finally, calculate the maximum current of the string so as not to exceed the Inverter’s MPPT circuit ratings.
Double check if the calculated Vmp range is within the 230-500 VDC optimal MPPT circuit operating range.
Consult a solar designer if needed.
FOR ALL MODULES, THE CALCULATIONS NEED TO BE PERFORMED OR VERIFIED BY USING A STRING CAL-
CULATOR OR CONSULTING A PROFESSIONAL.
The inverter has three MPPT PV charging circuits. MPPT #1 will use up to 25 amps which means two strings
can be paralleled for any modules having less than a 12.5 A (Imp) rating. MPPT #2 and MPPT #3 will use up
to 15 Amps each so they are usually limited to one string. (Unless you have a module with < 7.5 Amps)
Each string ideally should contain the same model, brand, and quantity of panels for ease of design, racking
and wiring. However, varying string sizes can be used for unique MPPTs. If two strings are used for MPPT
#1 they MUST be the same model, brand and # per string. MPPT#2 and MPPT #3 could differ in model,
brand and # per string (same make/model per string) on condition that each string complies with the low-
est temperature (maximum string number) and maximum amperage calculations above.
All panels on a series/parallel string should face the same orientation and hopefully be exposed to roughly
the same shading across the string. Consideration should be placed on string location and wiring order on
the racking to minimize shading effects. One shaded module can disproportionately reduce output for the
entire string so avoiding linear strings in favor of rectangular strings can increase output. Optimizers can
also achieve this.
The inverter will limit the total MPPT current to 25 A for MPPT #1 and to 15 Amps for MPPT #2 and 15
Amps for MPPT #3.
Note: The array can have a higher Imp than the 25A/15A specified, but the MPPTs will not make full use of
the extra current. Having an array that can produce more current than the MPPTs will bring in is useful for
increasing morning, winter or cloudy day solar production.

Table of Contents

Other manuals for EG4 18KPV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EG4 18KPV and is the answer not in the manual?

EG4 18KPV Specifications

General IconGeneral
ModelEG4 18KPV
CategoryInverter
Rated Power18 kW
Max. AC Output Current75A
Surge Power36 kW
Number of MPPTs2
Frequency50/60 Hz
Operating Temperature-25°C to 60°C
Warranty5 years
Output Voltage120/240VAC
CommunicationRS485
CoolingFan
Weight77 lbs (35 kg)
Dimensions670 x 530 x 220 mm

Related product manuals