EasyManua.ls Logo

Emerson DSM314 - COMM REQ Ladder Logic Example

Emerson DSM314
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual Appendix B
GFK-1742F Jan 2020
DSM314 Communications Request Instructions 409
B-5 COMM REQ Ladder Logic Example
The following ladder logic example is based upon the Parameter Load COMM REQ example
in the previous section. Refer to the table on the previous page for the Command Block
listing.
Setting up the COMM REQ Command Block Values
The next two rungs load the appropriate values into the first seven words of the COMM
REQ’s Command Block.
Figure 187
In the following two rungs, the remainder of the Command Block data is loaded. This data
is listed next:
%R00202 Command. For DSM, it’s always = E501 (hex)
%R00203 Parameter data size, in bytes = 68
%R00204 Memory type code for %R memory = 8
%R00205 Starting register for Parameter Data (offset by one) = 205
%R00206 Starting Parameter Number = 1

Table of Contents