User Manual Appendix E
GFK-1742F Jan 2020
Local Logic Execution Time 457
Table 97: Global Local Logic Variable Execution Times
X- Not Applicable
Local Logic Variable Name
Local Logic Execution Time (In Microseconds)
Read
Write
Local Logic Program Constants
0.50
X
Overflow
2.40
1.30
System_Halt
X
1.80
Data_Table_Ptr
0.60
0.70
Data_Table_sint
2.10
1.70
Data_Table_usint
1.80
1.70
Data_Table_int
2.30
2.20
Data_Table_uint
2.30
2.20
Data_Table_dint
3.80
4.00
Module_Error_Present
1.40
X
New_Configuration_Received
1.40
X
First_Local_Logic_Sweep
1.40
X
Module_Status_Code
0.50
X
CTL_1_to_32
0.50
X
P000-P255
0.60
0.60
D00-D07
0.70
0.70
CTL01-CTL32
1.40
1.80