User Manual Chapter 3
GFK-1742F Jan 2020
Installing and Wiring the DSM314 57
Table 16: IC693ACC335 Digital Axis Terminal Board Pin Assignments
* For signal names pertaining to servo axis 2, change all “_A” to “_B”.
Six 130V MOVs are installed between selected I/O points and the shield (frame ground) for
noise suppression. The I/O terminal points so connected are 6, 7, 8, 14, 15, and 16. The I/O
terminals support a wire gauge of 14-28 AWG. Maximum screw torque that may be applied
is 5 inch-pounds.
Note: Two of the screw terminals are labeled S for Shield. A short earth ground wire should be connected
from one of the S terminals directly to a panel earth ground. The cable shields for any shielded
cables from user devices should connect to either of the S terminals.