Technical data Proline Prowirl F 200 PROFIBUS PA
194 Endress+Hauser
Supply voltage Transmitter
An external power supply is required for each output.
The following supply voltage values apply for the outputs available:
Supply voltage for a compact version without a local display
1)
Order code for "Output" Minimum
terminal voltage
2)
Maximum
terminal voltage
Option G: PROFIBUS PA, pulse/frequency/
switch output
≥ DC 9 V DC 32 V
1) In event of external supply voltage of the PROFIBUS DP/PA coupler
2) The minimum terminal voltage increases if local operation is used: see the following table
Increase in minimum terminal voltage
Local operation
Increase in minimum
terminal voltage
Order code for "Display; Operation", option C:
Local operation SD02
+ DC 1 V
Order code for "Display; Operation", option E:
Local operation SD03 with lighting
(backlighting not used)
+ DC 1 V
Order code for "Display; Operation", option E:
Local operation SD03 with lighting
(backlighting used)
+ DC 3 V
Power consumption Transmitter
Order code for "Output" Maximum power consumption
Option G: PROFIBUS PA, pulse/frequency/
switch output
Operation with output 1: 512 mW
Operation with output 1 and 2: 2 512 mW
Current consumption PROFIBUS PA
15 mA
Power supply failure Totalizers stop at the last value measured.
Configuration is retained in the device memory (HistoROM).
Error messages (incl. total operated hours) are stored.
Electrical connection →  35
Terminals For device version without integrated overvoltage protection: plug-in spring terminals
for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
For device version with integrated overvoltage protection: screw terminals for wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)
Cable entries Cable gland: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
Thread for cable entry:
NPT ½"
G ½"