Proline Prowirl F 200 PROFIBUS PA Installation
Endress+Hauser 21
15 × DN
5 × DN
1
3
25 × DN
5 × DN
40 × DN
5 × DN
4
2
20 × DN
5 × DN
5
20 × DN
5 × DN
6
17 × DN + 8 × h
5 × DN
h
7
50 × DN
5 × DN
9
40 × DN
5 × DN
8
5 × DN
DN 25 (1"):≤
DN 40 (1½"):≥
A0019189
6 Minimum inlet and outlet runs with various flow obstructions
h Difference in expansion
1 Reduction by one nominal diameter size
2 Single elbow (90° elbow)
3 Double elbow (2 × 90° elbows, opposite)
4 Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
5 T-piece
6 Expansion
7 Control valve
8 Two measuring devices in a row where DN ≤ 25 (1"): directly flange on flange
9 Two measuring devices in a row where DN ≥ 40 (1½"): for spacing, see graphic
• If there are several flow disturbances present, the longest specified inlet run must
be maintained.
• If the required inlet runs cannot be observed, it is possible to install a specially
designed flow conditioner → 24.
The inlet run correction function:
• Makes it possible to shorten the inlet run to a minimum length of 10 × DN in the
event of flow obstructions 1 to 4. An additional measuring uncertainty of ±0.5% o.r.
occurs here.
• Cannot be combined with the wet steam detection/measurement application
package. If wet steam detection/measurement is used, the corresponding inlet runs
must be taken into consideration. It is not possible to use a flow conditioner for wet
steam.
Flow conditioner
If the required inlet runs cannot be observed, it is possible to install a specially designed
flow conditioner which can be ordered from Endress+Hauser. The flow conditioner is fitted