System integration Proline Prowirl F 200 PROFIBUS PA
68 Endress+Hauser
CHANNEL Input variable
69 Energy flow
465 Heat flow difference
Factory setting
Function block Factory setting: TOTAL
Totalizer 1, 2 and 3 Volume flow
Data structure
Input data of TOTAL
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Measured value: floating point number (IEEE 754) Status
SETTOT_TOTAL module
The module combination consists of the SETTOT and TOTAL functions:
• SETTOT: Control the totalizers via the PROFIBUS master.
• TOTAL: Transmit totalizer value, along with the status, to the PROFIBUS master.
Three Totalizer blocks are available (slot 5 to 7).
Selection: control totalizer
CHANNEL Value SETTOT Control totalizer
33310 0 Totalize
33046 1 Resetting
33308 2 Adopt totalizer initial setting
Factory setting
Function block Factory setting: Value SETTOT (meaning)
Totalizer 1, 2 and 3 0 (totalizing)
Data structure
Output data of SETTOT
Byte 1
Control variable 1
Input data of TOTAL
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Measured value: floating point number (IEEE 754) Status