PROline Promag 10 11 Description of Device Functions
Endress+Hauser 105
11.8 Group COMMUNICATION
Function description COMMUNICATION
! Note!
The Group COMMUNICATION is not available unless the option HART was selected in the
CURRENT SPAN function (Page 97)
TAG NAME Use this function to enter a tag name for the measuring device. You can edit
and read this tag name at the local display or via the HART protocol.
User input:
Max. 8-character text, permitted characters are: A-Z, 0-9, +,-, punctuation
marks
Factory setting:
“_ _ _ _ _ _ _ _” (no text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device. You can
edit and read this tag description at the local display or via the HART protocol.
User input:
Max. 16-character text, permitted characters are: A-Z, 0-9, +,-, punctuation
marks
Factory setting:
“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (no text)
FIELDBUS ADDRESS Use this function to define the address for the exchange of data with the HART
protocol.
User input:
0...15
Factory setting:
0
! Note!
Addresses 1...15: a constant 4 mA current is applied.
WRITE PROTECTION Use this function to activate HART write protection.
Options:
OFF = Function can be edited/read out via HART protocol
ON = HART protocol write protected (can only be read out)
Factory setting:
OFF
MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
Display:
17 (
11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display:
69 (
45 hex) for Promag 10