3.2.5 Foundations, supports
If the nominal diameter is DN 350, mount the sensor on a foundation of adequate load-
bearing strength.
"
Caution!
Risk of damage! Do not support the weight of the sensor on the metal casing.
The casing would buckle and damage the internal magnetic coils.
Fig. 13: Correct support for large nominal diameters (DN 350)
3.2.6 Adapters
Suitable adapters to (E) DIN EN 545 (double-flange reducers) can be used to install the
sensor in larger-diameter pipes. The resultant increase in the rate of flow improves
measuring accuracy with very slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by cross
section reduction:
!
Note!
The nomogram applies to fluids of viscosity similar to water.
1. Calculate the ratio of the diameters d/D.
2. From the nomogram read off the pressure loss as a function of flow velocity
(downstream from the reduction) and the d/D ratio.
Fig. 14: Pressure loss due to adapters
F06-10xxxxxx-11-05-xx-xx-000
F06-10xxxxxx-05-05-xx-xx-000