PROline Promag 10 11 Description of Device Functions
Endress+Hauser 97
11.6 Group CURRENT OUTPUT
Function description CURRENT OUTPUT
! Note!
The functions of the Group CURRENT OUTPUT are not available unless the value 0 was entered in the
FIELDBUS ADDRESS function (Group COMMUNICATION,Page 105)
CURRENT SPAN Use this function to define the current span. You can configure the current
output either in accordance with the NAMUR recommendation (max. 20.5 mA)
or for a maximum drive of 25 mA.
Options:
OFF
4-20 mA (25 mA)
4-20 mA (25 mA) HART
4-20 mA NAMUR
4-20 mA HART NAMUR
4-20 mA US
4-20 mA HART US
Factory setting:
4-20 mA (25 mA) HART
Current span, work range and signal on alarm level
A = Current span (option)
= Work range
= Lower signal on alarm level
= Upper signal on alarm level
= Scaled full scale value
Q = Flow
! Note!
If the measured value exceeds the measuring range (as defined in the
function VALUE 20 mA, Page 98) a notice message is generated
(#351, current span)
The current output's response to faults is defined in the central FAILSAFE
MODE function (Page 112).
20
0
I [mA]
Q
A
4-20 mA NAMUR
4-20 mA US
4-20 mA (25 mA)
3,8 - 20,5 mA
3,5 22,6
3,9 - 20,8 mA
3,75 22,6
4 - 24 mA 2 25
4-20 mA HART NAMUR
3,8 - 20,5 mA
3,5 22,6
4-20 mA HART US
3,9 - 20,8 mA
3,75 22,6
4-20 mA (25 mA) HART
4 - 24 mA 2 25
➁➂
OFF
4 mA
--
F06-10xxxxxx-05-xx-xx-xx-003