5 Operation PROline Promag 10
58 Endress+Hauser
50 Read assignment of the
device variables to the four
process variables
Access = Read
none Display of the current variable assignment of
the process variables:
Byte 0: device variable ID to the primary
process variable
Byte 1: device variable ID to the second
process variable
Byte 2: device variable ID to the third process
variable
Byte 3: device variable ID to the fourth
process variable
Factory setting:
Primary process variable: ID 1 for volume
flow
Second process variable: ID 250 for totalizer
Third process variable: ID 0 for
OFF (not assigned)
Fourth process variable: ID 0 for
OFF (not assigned)
53 Write device variable unit
Access = Write
This command sets the unit of the given device
variables. Only those units which suit the device
variable are transferred:
Byte 0: device variable ID
Byte 1: HART unit ID
ID of the supported device variables:
See data on Page 53
! Note!
If the written unit does not suit the device
variable, the device will continue with the last
valid unit.
If you change the unit of the device variable,
this has a direct impact on the system units.
The current unit of the device variables is
displayed in the device as a response:
Byte 0: device variable ID
Byte 1: HART unit ID
! Note!
Manufacturer-specific units are represented
using the HART unit ID “240".
59 Specify number of preambles
in message responses
Access = Write
This parameter specifies the number of
preambles which are inserted in the message
responses:
Byte 0: number of preambles (4...20)
As a response, the current number of the
preambles is displayed in the response
message:
Byte 0: number of preambles
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)