Proline Promag W 800 Electrical connection
Endress+Hauser 51
Sensor
Electrode cable Coil current cable
A
80 (3.15)
50 (1.97)
6 (0.24)
170 (6.69)*
20 (0.79)*
18.5 (0.73)
B
GND
³1 (0.04)
1
2
2
2
1
A0032100
A
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
160 (6.30)*20 (0.79)*
B
1
1
1
A0032101
A = Termination of the cables
B = Termination of the fine-wire cores with ferrules
1 = Red ferrules,  1.0 mm (0.04 in)
2 = White ferrules,  0.5 mm (0.02 in)
* = Stripping only for reinforced cables
7.3 Connecting the measuring device
L
WARNING
Risk of electric shock! Components carry dangerous voltages!
Have electrical connection work carried out by correspondingly trained specialists only.
Observe applicable federal/national installation codes and regulations.
Comply with local workplace safety regulations.
Observe grounding concept of the plant.
Never mount or wire the measuring device while it is connected to the supply voltage.
Before the supply voltage is applied, connect the protective ground to the measuring
device.
7.3.1 Connecting the remote version
L
WARNING
Risk of damaging electronic components!
Connect the sensor and transmitter to the same potential equalization.
Only connect the sensor to a transmitter with the same serial number.
Ground the connection housing of the sensor via the external screw terminal.
The following sequence of steps is recommended for the remote version:
1. Mount the sensor and transmitter.
2. Connect the connecting cable of the remote version.
3. Connect the transmitter.