Mounting procedure Proline Promag W 800
30 Endress+Hauser
30
25
20
10 15 20
[m]
[ S/cm]µ
L
max
[ ]ft
30 600 45
L
max
30
90
100
A0039272
2 Permitted length of connecting cable
Colored area
=
permitted range
L
max
=
length of connecting cable in [m] ([ft])
[µS/cm]
=
medium conductivity
Corrosive environment
The fully welded remote version of the device can be used permanently in a corrosive
(saline) environment.
The measuring device satisfies certified corrosion protection in accordance with EN ISO
12944 C5M. The fully welded design and the protective varnish guarantee use in a saline
environment.
6.1.3 Special mounting instructions
Display guard
‣
To ensure that the display guard can be easily opened, maintain the following
minimum head clearance: 350 mm (13.8 in)
Weather protection cover
213 (8.4)
39 (1.5)
243 (9.6)
203 (8.0)
A0029552
3 Weather protection cover; engineering unit mm (in)