DSG-423 ENGINE CONTROLS
08-2
GENERAL INFORMATION
GCP and Sensors
Engine Control Module (GCP)
The Engine Control Module (GCP) has the following
features:
• Programmable four speed electronic governing,
throttle-by-wire or variable speed control governing.
• Programmable emergency warning/shut-down
feature for high water temperature, low oil pressure,
etc.
• Starter lockout.
• Auto crank
• Programmable overspeed protection.
• Automatic altitude compensation.
• Sequential port fuel injection (gasoline) with
pressure regulator to precisely control fuel delivery.
• Dry fuel lockout controlled by the GCP produces a
reliable transition when switching fuels.
• Certified closed loop dry fuel control.
• Configurable inputs available based on customer
requirements.
• Configurable outputs available based on ECT, RPM
or MAP signals and customer requirements.
• Diagnostic software allows viewing of historical and
active faults with on-demand diagnostics to assist
technicians and reduce equipment downtime.
The Engine Control Module (GCP) engine control
system is a complete engine control system for Ford
industrial engines running on gasoline, propane or
natural gas. Each module can be set up to run an
engine on any two of the three fuels in certified closed-
loop control, with virtually transparent on-the-fly fuel
switching.
Each module can also be set up to run on a variety of
electronic governing:
• It can be programmed to provide up to four specific
speeds with use of a matching toggle switch.
• It can be programmed to provide an infinite variety of
CMP Sensor CKP Sensor TMAP Sensor HO2S Sensor KS Sensor ECT Sensor
GCP
Actuator Fuel Injector Ignition Coil