u For a power cable shorter than 20 m,
the one with a cross-sectional area of
16 mm
2
is recommended.
u For a power cable that is 20 m to 35
m long, the one with a cross-sectional
area of 25 mm
2
is recommended.
u For a power cable that is 35 m to 50
m long, the one with a cross-sectional
area of 35 mm
2
is recommended.
Note: The diameter of the PDP power
cable depends on the cable length and
the current actually carried by the PDP,
and hence should be determined
according to the project configuration.
0 V (16 mm
2
)
0 V (25 mm
2
)
0 V (35 mm
2
)
Connection
Table 9-3 Connections of the PDP (3000063) Power Cables
Cable Category
Cable Connector Connected to
Cable (blue) connecting to
the active -48 V power
supply in the equipment
room
1. Uninsulated ring
terminal
Active external power -48 V input
connector (-48V_A) of the PDP
2. Bare wire
-48 V connector of the active power
supply in the equipment room
Version: B
115