EasyManua.ls Logo

Filtec FT-70c - Error Number 117

Filtec FT-70c
243 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 8: Diagnostic and Repair Procedures
8-11
Error Number 117
This error condition indicates there is a Host or MODBUS Serial
Interface Framing Error or Reply Timeout (timeout must be a
minimum of 15 seconds.) Most communication errors are caused
by excessive noise.
Check the termination of RX input.
Check the baud rate (S2-1)
S2-1 CLOSED = 9600
S2-1 OPEN = 1200
Check the character size (S2-5)
S2-5 CLOSED = 8 bit, 1 stop.
S2-5 OPEN = 7 bit, 2 stop
Check the RX with a Voltmeter. Perform the check when the line is
in a steady state (No transmission).
RS-485
RX(-A) = GND
RX(+B) = +5VDC
RS-232
RX(-A) = -12VDC to -4VDC
RX(+B) = GND
Error Number 118
This error indicates a host or Modbus serial RX overrun error. The
baud rate may be set incorrectly.
To correct this error, check the baud rate setting which is controlled
by dip switches S2-1 and S2-4:
S2-1 closed = 9600 baud
S2-2 open = 1200 baud
Industrial Dynamics Company, Ltd. © Form 40256-0600

Table of Contents

Related product manuals