AC Wire Map Results
AC wire map results are similar to the wire map results shown in
Chapter 3. In some cases, the fault information given by AC wire
maps is less specific. For example, if a wire is shorted to a wire in
another pair, the AC wire map shows all four wires shorted. This
occurs because the AC electrical characteristics of some faults
prevent some types of measurements.
Figures 49 and 50 show examples of AC wire map screens.
When the tester cannot show the wire map because it has
multiple faults, it shows a list of the faults (see Figure 50).