EasyManua.ls Logo

Fluke DSX-600 - Change the NVP

Fluke DSX-600
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10: Custom Media and Test Limits
Change the NVP
185
Note
If you are on the NEW CUSTOM CABLE screen, tap
the NVP panel, then go to step 4 below.
To enter a specified NVP value
1 On the home screen, tap the test setup panel, tap a copper
test, then tap EDIT.
2 On the TEST SETUP screen, make sure that the Cable Type is
correct.
3 Under the Cable Type, tap NVP.
4 On the NVP screen, use or to change the NVP value.
5 Tap DONE, then tap SAVE.
Find a Cable's Actual NVP
To find a cable's actual NVP, you can use the NVP screen to adjust
the measured length to match a known length of cable. The NVP
value applies to the selected cable type.
To find a cable's NVP
Note
If you are on the NEW CUSTOM CABLE screen, tap
the NVP panel, then go to step 4 below.
1 On the home screen, tap the test setup panel, tap a copper
test, then tap EDIT.
2 On the TEST SETUP screen, make sure that the Cable Type is
correct.
3 Under the Cable Type, tap NVP.
4 Attach a channel adapter to the tester.
5 Connect a known length of twisted pair cable to the tester.
The cable must be a minimum of 30 m (100 ft) long.
-continued-

Table of Contents

Related product manuals