6-45
MHT260a (Engl.)
(c) T-link
Para. Name Setting range Initial value Change
96 Station number 0 to 99 (in 1 step) 1 Power
Sets the station number about communication.
Specifies the amplifier station number at 1 through 31 in decimal.
If the station number is hexadecimal, see the following conversion table.
Station No. setting
(decimal)
Station No. setting
(hexadecimal)
Station No. setting
(decimal)
Station No. setting
(hexadecimal)
Station No. setting
(decimal)
Station No. setting
(hexadecimal)
1 01H 11 0BH 21 15H
2 02H 12 0CH 22 16H
3 03H 13 0DH 23 17H
4 04H 14 0EH 24 18H
5 05H 15 0FH 25 19H
6 06H 16 10H 26 1AH
7 07H 17 11H 27 1BH
8 08H 18 12H 28 1CH
9 09H 19 13H 29 1DH
10 0AH 20 14H 30 1EH
31 1FH
If a fail-soft operation is reguired for SX bus type, specify the desired station number.
Use the initial value "0" as it is when the station number will be used in the system definition of D300win.
(19) System parameter 98Basic type, T-link
Para. Name Setting range Initial value Change
98 Binary/BCD 0: Binary 1: BCD 0 [Basic type]
1 [T-link]
Power
The code of values handled by the amplifier can be selected.
SX-bus type amplifiers handle binary code only.
The initial value of T-link type amplifier is 1 (BCD).