MHT260a (Engl.)9-9
(d) Cont (control signal) error
Keypad panel display
   
Contents of alarm
One and the same signal is allocated to several control input signal (CONTn) terminals on CN1 of amplifier.
Cause, check and remedy
Since the same signal cannot be allocated to several terminals, any one setting should be selected. Forced stop (10), free-run (54), external
fault input (34) and "not assigned" (0) may be present on several terminals. The same signal can be allocated to several control output
terminals.
Remark : The cont error does not occur in case of overlap setting of the CONT always valid 1, 2 (system para. 87, 88) and the system para.
A signal set at the CONT always valid is valid at all times.
(e) Low voltage, undervoltage
Keypad panel display
   
Contents of alarm
The voltage supplied to the amplifier is below the minimum specified level.
Cause, check and remedy
The supply voltage may have dropped on account of momentary failure, etc. or the power supply capacity may be poor.
Remark : The detection of undervoltage can be invalidated by setting of system para. 85 if the power supply condition is not good.
In this case, if free-run is selected by setting of system para. 84, the running can be continued at momentary failure.
(f) High voltage, overvoltge
Keypad panel display
   
      
   
Contents of alarm
The DC intermediate voltage in the amplifier is higher than the upper limit.
Cause, check and remedy
Overvoltage (Hv)
Contact us
Power-factor correcting capacitor
is turned on/off on same line ?
Occurs when turning on power ? Power supply voltage may be higher than specified.
Consider using AC reactor.
Braking resistor is connected ? Consider using external braking resistor (in case of 0.2 [kW] max.).
Braking resistor is disconnected ? Check the resistance of braking resistor.
For resistance of braking resistor, see 10.7.