CHAPTER 3
Small Configuration
Installing the 19-Inch (FC9682HSW3) Heat Baffle
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
3-52
Fujitsu and Fujitsu Customer Use Only
Figure 3-37 [p. 3-52] shows a right-side view of the heat baffle after the flange is mounted.
10 Secure the heat baffle to the rack using two rack mounting screws on each side of the
assembly.
Note: Ensure that the heat baffle is oriented as shown in Figure 3-30 [p. 3-47] so that air pushed
upward from below is deflected to the rear. If the heat baffle is mounted under the shelf, use the same
orientation so that air enters the shelf from the front of the rack.
This procedure is complete.
Figure 3-37: Flange Mounted on Right Side of Heat Baffle (23-Inch Rack Installation)
Front
m1656tj_1
Revision 1, June 2009