104 ADL300 • Functions description and parameters list
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.9 4524 MotorOT restart ENUM Disable 0 1 RW FVS
Enabling of automatic restart after the motor overtemperature alarm MotorOT.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.10 4526 MotorOT restart time ms UINT16 1000 120 30000 RW FVS
Setting of the time within which the Motor Overtemperature alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.11 4528 MotorOT holdoff ms UINT16 1000 0 30000 RW FVS
Setting of the delay between the signalling of the motor overtemperature alarm MotorOT and enabling of the alarm. If an
alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is removed within the set
time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.12 4540 Overspeed threshold rpm INT16 INT32 CALCI 0 CALCI RW FVS
Setting of the threshold above which the overspeed alarm Overspeed is enabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.13 4542 Overspeed activity ENUM Disable 0 4 RW FVS
Setting of the behaviour of the drive in case of a motor overspeed alarm Overspeed. This alarm indicates that the motor
speed has exceeded the threshold set in the Speed ref top lim and Speed ref bottom lim parameters in the COM-
MANDS menu.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.14 4544 Overspeed holdoff ms UINT16 0 0 5000 RW FVS
Setting of the delay between the signalling of the motor overspeed alarm Overspeed and enabling of the alarm. If an alarm
condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is removed within the set time,
the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.15 4550 SpdRefLoss threshold rpm INT16 100 0 CALCI RW FVS
Setting of the threshold below which the speed reference loss alarm SpdRefLoss occurs .
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.16 4552 SpdRefLoss activity ENUM Warning 0 4 RW FVS
Setting of the behaviour of the drive in case of a speed reference loss alarm SpdRefLoss. This alarm indicates that the
dierence between the speed regulator reference and the actual motor speed is more than 100 rpm.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.17 4554 SpdRefLoss holdoff ms UINT16 1000 0 10000 RW FVS
The delay between the Speed ref loss alarm condition signal and activation of the actual alarm. If an alarm condition oc-
curs, the drive will wait for the set time before enabling the alarm. If the alarm is removed within the set time, the drive will
not indicate any alarm condition.