106 ADL300 • Functions description and parameters list
Enabling of automatic restart after the drive heatsink overtemperature alarm HTsens.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.25 4584 HTsens restart time ms UINT16 20000 120 60000 ERW FVS
Setting of the time within which the HT sensor alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.26 4600 InAir activity ENUM Stop 0 4 ERW FVS
Setting of the behaviour of the drive in case of an intake air overtemperature alarm InAir. This alarm indicates that the
temperature of the intake cooling air is too high.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.27 4602 InAir restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the intake air overtemperature alarm InAir.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.28 4604 InAir restart time ms UINT16 1000 120 30000 ERW FVS
Setting of the time within which the Intakeair OT alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.29 4606 InAir holdoff ms UINT16 10000 0 30000 ERW FVS
Setting of the delay between the signalling of the intake air overtemperature alarm InAir and enabling of the alarm. If an
alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is removed within the set
time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.30 4610 Desat restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between the motor
phases or on the power bridge.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.31 4612 Desat restart time ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.32 4620 IOverC restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the drive Overcurrent alarm. This alarm indicates an overcurrent (or short circuit be-
tween phases or towards the ground).
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.33 4622 IOverC restart time ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Overcurrent alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 1000 msec).

Table of Contents

Other manuals for gefran SIEIDrive ADL300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive ADL300 and is the answer not in the manual?

gefran SIEIDrive ADL300 Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive ADL300
CategoryInverter
LanguageEnglish

Related product manuals