EasyManua.ls Logo

Honeywell C300 - Page 53

Honeywell C300
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
49
4. C300 Controller Configuration
4.2. Create C300 Controller and CEE function blocks
Step
Action
Result
8
In the Temperature High Alarm (degC)
field, accept the default or enter a value
at which an alarm is generated for
controller hardware high temperature.
Press <Tab>.
Note setting this value at 0 disables the
temperature high alarm.
Moves cursor to the CPU Free Low
Alarm (%) field.
9
Accept the default or enter the desired
value. Press <Tab>.
Note: Do not set lower than the default
value of 20%.
Moves cursor to Simulation Node
Configuration section.
10
If this block is to be loaded to a
simulation environment, select the Load
to simulation Environment check box.
Press <Tab>.
Moves cursor to Host IP Address field
11
If the controller is to be a SIMC300
controller you must enter the IP Address
of the SIMC300 controller. Press <Tab>.
Moves the Cursor moves to the Host
Name field.
12
Enter the host name of the SIMC300
controller if it does not appear in the field.
13
Click Server History tab.
The Server History configuration form
appears.

Table of Contents

Related product manuals