Series 8 C300 Controller User's Guide
Honeywell
4. C300 Controller Configuration
4.3. Configure CEEC300 block
Select the Base Execution Period
from the drop-down list. Press <Tab>.
Note: Prior to selecting the IOLINK
configuration for the controller, the
base execution period must be
selected. Otherwise, an error
message appears as follows: "CEE
BASEPERIOD cannot be changed
because IOLINK TYPE of at least one
IOLINK of this C300 has been
configured.”
Moves cursor to User Lock for CEE Run
field.
Note that CEE Command field is available
only in Monitor mode.
Accept the default or select desired
user from the drop-down list. Press
<Tab>.
Moves cursor to User Lock for CEE Idle
field.
Accept the default or select the
desired user from the drop-down list.
Press <Tab>.
Moves cursor to Program Access may
command CEE from Idle to Run check box.
Select the check box to enable
access. Press <Tab>.
Moves cursor to Program Access may
command CEE from Run to Idle check box.
Select the check box to enable
access. Press <Tab>.
Moves cursor to the Alarming Enabled
check box.
Accept the default (Alarming
Enabled), or clear the box to disable
alarming function. Press <Tab>.
Moves cursor to the Enable Memory Limit
Exceeded Alarm check box.
Accept the default (Memory Limit
Exceeded Alarm enabled), or clear
the box to disable alarming function.
Press <Tab>.
Moves cursor to the CEE State under the
Powerup Restart Settings section.
Accept the default or select the
desired state from the down-down list
list.
Note that if you select LASTTIMEOUT state,
then the Warm Timeout field is active.
If the Warm Timeout field is active,
accept the default or enter the desired
timeout value. Press <Tab>.
Moves cursor to the Time Zone field.