GX-Series Control Panel Installation and Setup Guide
6-101
NOTE: If groups are enabled a failure on the primary path will not provide specific IP information. Options are
available to select specific paths or all paths.
1 = Primary
When selected the Ethernet module will only monitor the primary transmission path. All other
transmission paths will not be monitored.
2 = Secondary
When selected the Ethernet module will only monitor the secondary transmission path. All other
transmission paths will not be monitored.
3 = Alarm Mon.
When selected the Ethernet module will only monitor the Alarm Mon. transmission path. All other
transmission paths will not be monitored.
4 = Any
When selected the Ethernet module monitors all transmission paths. If a supervision failure is
detected in any of the paths a line fail condition will be activated.
5 = All
When selected the Ethernet module monitors all transmission paths. If a supervision failure is
detected in all of the paths a line fail condition will be activated.
56.4.08 = SIA Control
When using the SIA control command protocol for integration purposes the IP address of the computer
sending the SIA control commands should be entered in this field to ensure that only commands from a
computer with the programmed IP address will be recognized by the Ethernet module.
1 = IP Address
The address will be in the form XXX.XXX.XXX.XXX. The dot separator will be automatically added after
each sequence of three numbers or can be manually added by pressing the * key.
56.4.09 = Encrypt
NOTE: This option is not for use in UL installations.
The Ethernet module supports a high level 128bit encryption algorithm for all communication options. This
option allows encryption to be enabled/disabled for each of the communication options.
1 = Alarm Report
This option controls encryption for the Primary and Secondary alarm transmission paths. Default is
disabled.
0 = Off
If selected encryption is disabled for the Primary and Secondary alarm transmission paths.
1 = On
If selected encryption is enabled for the Primary and Secondary alarm transmission paths. In order
for data to be received when this option is selected the receiver must support decryption.
2 = Remote Access
This option controls encryption for the Remote Servicing sessions. Default is disabled.
0 = Off
If selected encryption is disabled for the Remote Servicing sessions.
1 = On
If selected encryption is enabled for the Remote Servicing sessions. In order for data to be received
when this option is selected the receiver must support decryption.
3 = SIA Control
0 = Off
This option controls encryption for communications between the Ethernet module and remote PC
using the SIA control command protocol. Default is disabled.
1 = On
If selected encryption is enabled for communications between the Ethernet module and remote PC
using the SIA control command protocol. In order for data to be received when this option is selected
the receiver must support decryption.