EasyManua.ls Logo

Honeywell GX-Series - Page 95

Honeywell GX-Series
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GX-Series Control Panel Installation and Setup Guide
6-49
This is the total number of zone activations logged in any one set (armed) period. The selectable values
are 0-10 where 0 is unlimited. {A value of 0 is required for UL installations.}
2 = Unset Limit
This is the number of activations logged from any one zone in any one unset (disarmed) period. The
selectable values are 0-7. The default is 3.
Fire alarms are not restricted by this parameter.
3 = Set Limit
This is the number of activations logged from any one zone in any one set (armed) period. The selectable
values are 0- 7. The default is 3.
Fire alarms are not restricted by this parameter.
NOTE: This feature only affects Contact ID, SIA and Microtech communication formats.
49 = Confirm Time {Not for UL installations}
This option is the maximum time between two separate zones for a confirmed alarm to be generated up to a
maximum of 99 minutes, which is equivalent to the complete set (armed) period, with a default of 30
minutes.
50 = NOT USED
51 = NOT USED
52 = NOT USED
53 = NOT USED
54 = Keypad Access
This option allows the keypad to unset (disarm) the system. There are two options:
1 = Always
2 = Except Entry: Except when entry time is running. This ensures that users are unsetting
(disarming) using a proximity card (portable device).
55 = Confirm
This option controls how confirmed alarms are generated. It controls the operation of confirm outputs plus
the signaling of confirmed alarms. There are three options:
1 = Operation: This option controls when confirmed alarms can be triggered. An entry timeout alarm
will never contribute to a confirmed alarm. There are three options:
1 = Before Entry. Confirmed alarms can be triggered before starting entry time only.
2 = Except entry (UK). Confirmed alarms can be triggered any time except during the entry delay
period.
3 = Always (EU). Confirmed alarms are always enabled.
2 = Entry Timeout: This option controls whether exit type zones can cause confirmed alarms, after an
entry timeout.
0 = Disable Exits. Exit type zones will only cause unconfirmed intruder alarms. They will not
contribute to the two activations required for a confirmed alarm.
1 = Enable Exits. After the expiration of the entry delay, activation of an exit type zone will be
identical to an intruder zone.
3 = Reduce Reset: This option allows user reset following an unconfirmed alarm.
0 = Off. Full system reset is required for any intruder alarm.
1 = On Unconfirmed. The system can be reset by user, if the alarm is unconfirmed. If the alarm is
classed as confirmed, a full system reset will be required.
56 = Force Restore
This option dictates when intruder restore signals are transmitted.
1 = Unset/Unconfirm: On unset (disarming) or at the end of the confirmed time if the alarm is not
confirmed.

Table of Contents

Related product manuals