Input Calibration
92 UDC2300 Controller Product Manual 12/00
0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volt Inputs
Use the copper leads and connect the calibrator to the rear terminals of Input #2
(see Figure 8-8).
Make sure the jumper of S201 is set for Volts (position 2).
See Figure 2-2 Jumper Placements.
24879
15
16
+
_
1 to 5 Volt
Source
+
_
Copper
Leads
0 2 Volts
0 5 Volts
Figure 8-8 Wiring Connections for 1 to 5 Volt Input Input 2
8.7 Input 2 Calibration Procedure
Preliminary Steps
Apply power and allow the controller to warm up for 30 minutes before you calibrate.
Please read Subsection 8.6 Input 2 Set Up Wiring before beginning the procedure.
Make sure you have LOCK set to NONE. See Subsection 4.5 - Tuning Set Up
Group.
Continued next page