Configuration
36 UDC2300 Controller Product Manual 12/00
4.11 Control Set Up Group
Introduction
The functions listed in this group deal with how the controller will control the process
including: Number of Tuning Parameter Sets, Setpoint Source, Tracking, Power-up
Recall, Setpoint Limits, Output Direction and Limits, Deadband, and Hysteresis.
Function Prompts
Table 4-10 CONTRL Group (Numeric Code 800) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
PIDSET 801
Number of Tuning
Parameter Sets
0
1
2
3
ONE
2KBD (Keyboard)
2 PR (PV switch)
2 SP (SP switch)
ONE 146
SW VAL 802
Automatic
Switchover Value
Value in engineering units
within PV or SP range limits
0.00 156
LSPS 803
Local Setpoint
Source
0
1
ONE
TWO
ONE 141
RSPSRC 804
Remote Setpoint
Source
0
1
NONE
INP2
NONE 150
SP TRK 805
Setpoint Tracking 0
1
2
NONE
PROC (LSP tracks PV
manual)
RSP (LSP tracks RSP
auto)
NONE 155
PWR UP 806
Power Up Controller
Mode Recall
0
1
2
3
4
MAN (Manual/LSP/failsafe)
ALSP (Auto/last LSP)
ARSP (Auto/last RSP)
AMSP (Last mode/last SP)
AMLS (Last mode/last LSP)
MAN 148
PWROUT 807
TPSC (Three
Position Step
Control) Output
Start-up Mode
0
1
LAST (Last output)
FSAF (Failsafe output)
LAST 147
SP Hi 808
Setpoint High Limit 0 to 100 % of the PV range 2400 153
SP Lo 809
Setpoint Low Limit 0 to 100 % of the PV range 0 153
ACTION 810
Control Output
Direction
0
1
DIR
REV
REV 120