Honeywell UDC2300 - Table 10-7 Troubleshooting Time Proportional Output Failure

Honeywell UDC2300
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting/Service
110 UDC2300 Controller Product Manual 12/00
Procedure #3
Table 10-7 explains how to troubleshoot Time Proportional Output failure.
Table 10-7 Troubleshooting Time Proportional Output Failure
Step What to do How to do it
1
Make sure the controller is configured
for Time Proportional output.
Make Output Algorithm Set Up group function
prompt OUTALG = RLY or RLYD.
Refer to Section 4 - Configuration.
2
Check the field wiring. Make sure the NO or NC contact selection is
correct.
Refer to Section 2 - Installation for details.
3
Check the output (control) relay
jumper position.
Refer to Section 2 Installation for relay jumper
placement and relay contact information.
4
Check the output. Put the controller into Manual mode. Vary the
output above and below the present value.
Observe OUT indicator on the operator interface.
Contact should change state. 1E 0 % open, 100 %
closed.
5
Check relay. Change relay.
6
Change Main board. Installation instructions supplied with the new
board.