Operation
12/00 UDC2300 Controller Product Manual 69
6.13 Setting Failsafe Mode
Introduction
You can set the Failsafe Mode to be Latching or Non-Latching.
Set Failsafe Mode
Table 6-16 Procedure for Setting a Failsafe Mode
Step Operation Press Result
1
Select Control
Set-up Group
SET UP
Until you see:
Upper Display = SET
Lower Display = CONTRL
2
Select Failsafe
Function Prompt
FUNCTION
You will see:
Upper Display =
LACH (Controller goes to manual and output goes to
failsafe value)
NO L (Controller mode does not change and output goes
to failsafe value)
Lower Display = FSMODE
3
Select a value [] [] To select a failsafe mode in the upper display.
4
Return to Normal
Display
DISPLAY
At power up, the output will go to the value set.