Configuration
12/00 UDC2300 Controller Product Manual 35
4.10 Input 2 Set Up Group
Introduction
This data deals with various parameters required to configure Input 2.
Function Prompts
Table 4-9 INPUT2 Group (Numeric Code 700) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
IN2TYP 701
Input 2 Type 0
25
26
29
30
34
DIS
0-20 (mA)
4-20 (mA)
0-5 (Volts)
1-5 (Volts)
0-2 (Volts)
1-5V 140
Numeric English Numeric English
XMITR2 702
Transmitter
Characterization
for
Input 2
0
1
2
3
4
5
6
7
8
9
10
11
12
B
E H
E L
J H
J L
K H
K L
NNMH
NNML
N90H
N90L
NIC
R
13
14
15
16
17
18
19
20
21
22
23
24
25
S
T H
T L
W H
W L
100H
100L
200
500
RADH
RADI
LIN
SrT
LIN 159
Numeric English
IN2 HI 703
Input 2 High
Range Value
999 to 9999 floating in
engineering units
2400 139
IN2 LO 704
Input 2 Low Range
Value
999 to 9999 floating in
engineering units
0 139
RATIO2 705
Ratio on Input 2 -20.0 to 20.0 1.00 149
BIAS 2 706
Bias on Input 2 -999 to 9999 0.0 125
FILTR2 707
Filter for Input 2 0 to 120 seconds
0 = No Filter
1.0 134

Table of Contents