Configuration
38 UDC2300 Controller Product Manual 12/00
4.12  Options Set Up Group
Introduction
The Options group lets you configure the remote mode switch (Digital Inputs) to a
specific contact closure response, or configure the Auxiliary Output to be a specific
selection with desired scaling.
Function Prompts
Table 4-11 Options Group (Numeric Code 900) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
AUXOUT 901
Auxiliary Output 0
1
2
3
4
5
6
7
DIS Disabled
IN1 Input 1
IN2 Input 2
PROC Process Variable
DEV Deviation
OUT Output
SP Setpoint
LSP1 Local Setpoint 1
DIS 122
0 PCT 902
Auxiliary Output
Low Scaling Factor
Value in Engineering Units 0 119
100 PCT 903
Auxiliary Output
High Scaling
Factor
Value in Engineering Units 100 119
DIG IN 904
Digital Input
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
None
MAN To Manual
LSP To Local SP 1
SP2 To Local SP 2
DIR Direct Control
HOLD Hold SPP/SP Ramp
PID2 PID Set 2
RUN Start a stopped
SPP/SP Ramp
Begn SPP Reset
NO I Inhibit Integral
MNFS Manual, Failsafe
Output
LOCK Keyboard Disable
TIMR Start Timer
TUNE Start Tune
INIT Init SP to PV
RSP Remote SP
MNLT Latching Manual
TRAK Output tracks Input 2
NONE 131
DI COM 905
Digital Input
Combinations
0
1
2
3
4
5
DIS Disable
+ PD2 PID Set 2
+DIR Direct
+SP2 Set Point 2
+SP1 Set Point 1
+RUN Start SPP
DIS 131