Monitoring
50 UDC2300 Controller Product Manual 12/00
Viewing the operating parameters
Press the
DISPLAY key to scroll through the operating parameters listed in Table 5-3. The
lower display will show only those parameters and their values that apply to your specific
model.
Table 5-3 Lower Display Key Parameter Prompts
Lower Display Description
OT
OUTPUTOutput value is percent; for Three Position Step control, this is an
estimated motor position when no slidewire exists.
SP
LOCAL SETPOINT #1Also current setpoint when using SP Ramp.
2L
LOCAL SETPOINT #2
RS
REMOTE SETPOINT
2ND
INPUT 2
DE
DEVIATIONMaximum negative display is 999.9.
PIDSX
TUNING PARAMETER SELECTED SETwhere X is either 1 or 2.
TIME REMAININGTime that remains on timer in Hours.Minutes
ELAPSED TIMETime that has elapsed on timer in Hours.Minutes.
RPXXXM
SETPOINT RAMP TIMETime remaining in the setpoint ramp in minutes.
AX
AUXILIARY OUTPUT
Sn
SP RATE SETPOINTCurrent setpoint for setpoint rate applications
BI
BIASDisplays the manual reset value for algorithm PD+MR.
To BGn
TO BEGINResets Setpoint Program back to beginning of the program.