Input Calibration
86 UDC2300 Controller Product Manual 12/00
Check the Jumper for Input 1
Before you calibrate Input #1, check the internal jumper for Input 1 to make sure it is set
for the correct input type. The jumper is located at position S101 on the printed wiring
board. Figure 2-2 shows the location of the jumper and position selections.
Check the Jumper for Input 2
Before you calibrate Input #2, check the internal jumper for Input 2 to make sure it is set
for the correct input type. The jumper is located at position S201 on the printed wiring
board. Figure 2-2 shows the location of the jumper and position selections.
Equipment Needed
Table 8-2 lists the equipment you will need to calibrate the specific types of inputs that
are listed in the table. You will need a screwdriver to connect these devices to your
controller.
Table 8-2 Equipment Needed
Type of Input Equipment Needed
Thermocouple
Inputs (Ice Bath)
A calibrating device with ± 0.02 % accuracy for use as a signal
source such as a millivolt source.
Thermocouple extension wire that corresponds with the type of
thermocouple that will be used with the controller input.
Two insulated copper leads for connecting the thermocouple
extension wire from the ice baths to the mV source.
Two containers of crushed ice.
Thermocouple
Inputs (T/C Source)
A calibrating device with ± 0.02 % accuracy for use as a signal
source such as a millivolt source.
Thermocouple extension wire that corresponds with the type of
thermocouple that will be used with controller input.
RTD (Resistance
Thermometer
Device)
A decade box, with ± 0.02 % accuracy, capable of providing stepped
resistance values over a minimum range of 0 to 1400 ohms with a
resolution of 0.1 ohm.
Three insulated copper leads of equal length for connecting the
decade box to the controller.
Milliampere,
Millivolt, Volts, and
Radiamatic
A calibrating device with ± 0.02 % accuracy for use as a signal
source.
Two insulated copper leads for connecting the calibrator to the
controller.
Place current source at zero before switching ON.
Do not switch current sources OFF/ON while connected to the
UDC2300 input.
ATTENTION: For radiamatic inputs only, set emissivity value to 1.0.
See Subsection 4.9 Configuration Set Up prompt INPUT1, function
prompt EMISS.